Mobile Power

mobile-generator

Like the our Stationary Power Units, our Mobile Power Units surpass the standard for heavy duty base load generation equipment, when efficiency and reliability are necessities.

The MPU Mobile Power Unit comes with the only 3 MW medium speed reciprocating engine driven generator set in a 44′ steel container available.

mobile power unit middle

These industrial strength generator sets are well-suited for critical need power requirements in remote areas and offer the lowest operating and maintenance costs you can find on the market.

The MPU is available in continuous output ratings of 1500 kW, 2000 kW, 2500 kW, and 3000 kW. All units feature an additional power reserve of 10% for standby. All units are able to accept instantaneous block loads of 110% of the continuous output rating.

mobile power unit right

The MPU Generator Set is designed to handle heavy duty industrial and utility power applications. These units are ideal for utility grade power needs of 1500 kW – 100 MW +.

All units come with the equipment needed to generate power including auto paralleling switchgear, advanced controls for local and remote operation / monitoring of single and multiple unit installations.

mobile power unit left

These proven mobile power units, in additional to our excellent technical support and continuous maintenance offerings make the MPU the optimal power station for your mobile power requirements.

Engine

Manufacturer    .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .   GM/EMD

Type    .  .  .  .  .   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .     2 Cycle, V-45

Fuel Type   .  .   .  .  . HFO Bio-Diesel,  Diesel, Natural Gas, Dual Fuel

Model  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  Series 645 & 710

Number of Cylinders  .  .  .  .  .  .  .  .  .  .  .  .  .    8, 12, 16 & 20 Cylinder

Bore   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .    9-1/16th inch

Stroke     .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .   X 10 inch

Displacement   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .    645 cubic inches

Piston Speed    .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .    1,500 ft. / min

Engine Speed   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .   750 – 900rpm

Governor   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  Electronic – Woodward – EG

Starting Motor   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .       Air,  or DC

Control Power      .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .120VAC & 24VDC

Generator

Manufacturer  ,  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .    Baylor

Type   .  .  .  .  .  .  .  .  .  .    Brushless, insulated single roller bearing

Insulation   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .     NEMA Class F

Construction   .  .  .  .  .  .  .  .  .  .  .   Vacuum Pressure Impregnation

Enclosure   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  Drip Proof  Temperature Rise  (continuous @ .7 PF)  .  .   .  .  .  .  80 degrees C

Exciter    .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .   .   PMG

Voltage Regulator   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .   Basler,  SSR-12

Weight  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .   . 18,700 lbs

Electrical Rating .  .  .  .  500kW, 2000kW, 2500kW ,3000kW & 4400kW cont.

Weights & Dims

Length  .  .  .  .  .  .  40-44 feet

Width    .  .  .  .  .  .  .  .     8 feet

Height   .  .  .  . 13 feet 6 inches

Weight  .  .   92 to 115,000 lbs

Heat Rate MPU Models

Diesel, HFO, Bio-diesel

9240 BTU/kW/hr

Natural Gas

9,600 BTU/kW/hr

Controls

Digital/PLC/HMI with manual & hot back ups The Control Sys 2000 Protection

Complete Engine,  Generator and Utility Grade Protection Package with Remote Controls  and  Alarming  Package and Advanced Operations and Maintenance System Program and Software